CONTROL SYSTEM PRODUCTS

- REMOTE INTELLIGENCE & COLOR TOUCH SCREEN HAS BEEN ADDED -

NEW - | W1800 Remote Telemetry Unit  | - NEW

We are happy to announce the second of a series of new Remote Telemetry Unit's.  When applied in conjunction with our Windows based Human Machine Interface and machine level Visual Logic Controller this RTU will offer our customer cost savings, ease of use and an extended control system life cycle.  The W1800 product was developed as an Industrial Grade Mid-range (1 to 64 I/O count) RTU.  Remote user configurable intelligence and a Color Touch Screen has been added to this RTU's capabilities making it a full featured RTU and extending it's I/O counts.  W1800 RTU's use computer standard RS232 serial ports which are normally configured to communicate at baud rates of 600 or 1200 bps.  The W1800 includes the necessary bridging to interface directly to a standard off the shelf mobile Radio and/or dedicated phone line.  The RTU is of current technology and design consisting of robust hardware and firmware. 

W1800_b.jpg (108374 bytes)

The initial W1800 RTU configuration offers up to thirty two I/O modules of two I/O channels per module for a total of sixty four (64) I/O.  Each of the 32 Modules may be Digital Input, Digital Output, Analog Input or Analog Output.  The I/O system is made up of up to two Grayhill Open Line I/O Brain boards driving up to two I/O racks per Brain board.   Each Digital Input may be configured to maintain and report back the status of local accumulators for both Starts and Run Times.  Configuration of the W1800 is accomplished from a local Laptop computer using the RS232 serial communications port labeled TEST.  The configurator software is Windows based and is very user friendly. This product has been designed to accommodate Fiber Optic, Cellular and Cable modems, should they become the data communications link of choice in the future.

The intelligent W1800 RTU configuration allows the user to implement RTU local filter backwash or backup logic at the RTU location with a 6 to 10" black and white or color touch screen operator interface.  This option brings the W1800 to a new full featured level of operation.  The I/O count on this version increases to approximately 256.

SPECIFICATIONS:

TELEMETRY COMMUNICATIONS:

POLLED: Computer standard RS232 / RS485 port is used to respond to Master queries using non-proprietary ASCII telemetry protocol.  The protocol used, consists of start characters, master address, RTU address, CRC data security, word count, parity checks, data and stop bits.  The entire communication cycle takes less time than changing one I/O point using Modbus protocol and a PLC.   The telemetry port provides direct serial interface to both standard mobile radios and dedicated phone lines.  An RS485 port is used for I/O communication to the Grayhill I/O systems up to 4000 feet from the RTU.  The master control Computer continuously updates the data from all RTU's, treating missed communications as a Data Fail alarm condition.  The Customer is notified of all alarm conditions immediately by the control computer.

POWER: 12 VDC Industrial grade power supply | Power indicator (Green LED) | Internal Battery: 3 volt lithium maintains EPROM RTU configurations and local accumulators. 

TEMPERATURE: 10 deg. F to 130 deg. F operating | 0 deg. F to 130 deg. F storage.

HUMIDITY: 0-90% RAH., non-condensing.

SURGE: 2500 V / ANSI   EMI / RFI: Exceeds FCC part 15c

ENCLOSURE: METAL SHELL: (4.5" wide, 4.05" high x 1" deep)  DIN rail mount.

DIGITAL AND ANALOG I/O:

I/O is accomplished using Grayhill Open Line removable I/O modules for AI, AO, DI and DO.  Analog inputs and outputs are available using most standard current and voltage configurations example: 4-20ma or 1-5volts.  Digital inputs and outputs are available a wide variety of AC and DC voltages and isolation configurations. 

 

| W1600 Remote Telemetry Unit  |

The W1600 was the first of a series of new Remote Telemetry Unit's.  When applied in conjunction with our Windows based Human Machine Interface and machine level Visual Logic Controller this RTU offers our customer cost savings, ease of use and an extended control system life cycle.  This RTU was developed as an Industrial Grade base line (low I/O count) version of our new series of RTU's.    W1600 RTU's communicate at baud rates of 1200 to 115kbps using Computer standard RS232 or RS485 serial ports.  The RTU is of current technology and design consisting of robust hardware and firmware.

The W1600 RTU offers eight (8) I/O channels which may be user configured as either a Digital Input or Digital Output.  Two (2) of the eight I/O channels may be configured as either an Analog Input or Analog Output.  Each Digital Input or Output may be configured as N/O or N/C.  Each Digital Input may be configured to maintain and report back to the system server computer the status of local accumulators for both Starts and Run Times when a communication is made.  Configuration of the W1600 is accomplished from the Master computer or a local Laptop computer using one of the serial communication ports.  This product has been designed to connect directly to Fiber Optic, Cellular and Cable modems, should they become the data communications link of choice in the future.

SPECIFICATIONS:

TELEMETRY COMMUNICATIONS:

POLLED: Computer standard RS232 / RS485 port is used to respond to Master queries using non-proprietary ASCII telemetry protocol.  The protocol used, consists of start characters, master address, RTU address, CRC data security, word count, parity checks, data and stop bits.  The entire communication cycle takes less time than changing one I/O point using Modbus protocol and a PLC.   The telemetry serial port is configured as an RS232 port when the RTU is at a remote location.  The RS232 port is tied directly to a data radio or through a miniature Bell 202 modem when using an analog radio or dedicated phone lines.  The RS485 port configuration is used for multiple local RTU connections up to 4,000 feet from the master computer.  The master control Computer continuously updates the data from all RTU's, treating missed communications as a Data Fail alarm condition.  The Customer is notified of all alarm conditions immediately by the control computer.

QUIESCENT: Computer standard RS232 / RS485 port is used to contact the Monitoring computer using the same non-proprietary ASCII telemetry protocol as the polled operation.  The master computer system is configured for quiescent operation on the serial port tied to the quiescent RTU's and other than an occasional RTU verification waits for event driven communications from the RTU's in the same way a PLC system would.  Event driven telemetry communications should not be used for real time or mission critical operations.

POWER: 12-24 VDC @ 1 amp (UL/CSR rated wall plug-in power supply) | Power Fail indicator (Red LED) | Internal Battery: 3 volt lithium to maintain a Y2K compliant real time clock |  External Battery: 12 volt 1.8 ah sealed lead acid to provide 12 hour (typical) battery backup | 12 volt Fast charge regulated battery charger | Compatible with Solar power interface | Power & Battery on/off switch.

TEMPERATURE: 10 deg. F to 130 deg. F operating | 0 deg. F to 130 deg. F storage.

HUMIDITY: 0-90% RAH., non-condensing.

SURGE: 2500 V / ANSI   EMI / RFI: Exceeds FCC part 15c

ENCLOSURE: METAL SHELL: (7.7" wide, 8.8" high x 4" deep) Suitable for panel or enclosure mount (8" x 11" std.). 

DIGITAL AND ANALOG I/O:

I/O is accomplished using Grayhill Open Line removable I/O modules for AI, AO, DI and DO.  Analog inputs and outputs are available using standard 4-20ma or 1-5volts modules.  Digital inputs and outputs are available a wide variety of AC and DC voltages and isolation configurations. 

| W2000 PC Remote Telemetry Unit  |

The Large scale RTU of this series is in the field, proving it's worth and already exceeds all known PLC and RTU specifications in capabilities, serviceability, telemetry speeds, I/O counts and user configurability.  The W2000 PC-RTU prices out significantly less than a full blown PLC.  The first Field units were installed in 2000 and have been performing mission critical tasks in a Real Time environment around the clock.

 